The Hager MM508N three-phase thermal-magnetic motor circuit breaker is designed to protect motors. For a three-phase motor, its rated AC-3 power is 0.75 kW at 400 V and 1.5 kW at 230 V.
- Type: Thermal-magnetic motor circuit breaker
- Phases: 3
- Current adjustment range: 2.5–4.0 A
- Rated insulation voltage: 690 V
- Impulse withstand voltage: 6000 V
- Total power loss at rated current In: 5.33 W
- Rated power of a three-phase motor in AC-3 at 400 V: 0.75 kW
- Rated power of a three-phase motor in AC-3 at 230 V: 1.5 kW
- Electrical endurance: 50000 operating cycles
- Mechanical endurance: 40 operations per hour
- Number of mechanical operations: 100000