The ABB MS116-6.3 thermal-magnetic circuit breaker is used to switch motors on and off, and to protect them against short circuits, overloads and phase failures, without a fuse. The motor’s rated current is set using the selector on the device. It is suitable for single-phase and three-phase applications.
- Current setting range: 4.0–6.3 A
- Rated operating current: 6.3 A
- Instantaneous short-circuit current setting: 78.8 A
- Rated operational voltage: 690 V AC
- Rated insulation voltage: 690 V
- Rated impulse withstand voltage: 6 kV
- Short-circuit breaking capacity Ics: 50 kA at 230 V AC and 400 V AC, 6 kA at 440 V AC and 500 V AC, 2 kA at 690 V AC
- Ultimate short-circuit breaking capacity Icu: 75 kA at 230 V AC and 400 V AC, 18 kA at 440 V AC, 15 kA at 500 V AC, 3 kA at 690 V AC
- Trip class: 10A
- Rated operating power AC-3: 2.2 kW at 400 V, three-phase
- Poles: 3
- Electrical endurance: 100,000 cycles
- Mechanical endurance: 100,000 cycles