The ABB 25319 air-break switch is a capacitor relay for installations where the peak current can greatly exceed 100 times the rated operating current. The contacts are supplied with damping resistors and are used without additional inductors.
Before re-energizing, the capacitors must be discharged, with a maximum residual voltage of 50 V at the terminals. The electrical endurance of the contacts is 250,000 operating cycles.
- Type: Capacitor relay
- Rated capacitor power: 50 kVar
- Control voltage: 230 VAC
- Current at 440 V: 1,300 A
- Power factor at 440 V: 0.45
- Current at 690 V: 630 A
- Power factor for current above 100 A: 0.35
- NO contact opening time: 4–11 ms after coil de-energization
- NO contact closing time: 8–27 ms after coil energization