In August, I bought the above ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W), to be installed EXCLUSIVELY on the EPSON TW9200W projector.
I bought it solely for the safety of the projector and intentionally chose a ups with 100w more than the Epson's requirements to cover it without any issues.
According to the ups technical specifications, it is for 480w and the projector operates at full capacity at 334w (though it operates in economy mode at 270w).
Now, with the storms that caused power outages, I needed it three times and all three times it did not keep the projector on at all, so I couldn't safely turn it off to avoid any damage to the projector and lamp due to temperature.
To check it better, a test was conducted on the ups with a 60-inch LG PB5600 plasma TV with power consumption in operation: 154 Watts and there was no problem at all, it held power normally until the TV safely turned off. The same test was done on a smaller Epson TW600 projector with power consumption in full operation: 250 Watts, and it held power normally there as well, so that the projector could be safely turned off.
Logically, with the above examples, it should not be able to handle more than 300w, even though it is stated to handle up to 480w.
After receiving an email from the company regarding the above "issue": We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
Τον Αυγουστο αγορασα το παραπανω ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W) ,για να τοποθετηθεί ΑΠΟΚΛΕΙΣΤΙΚΑ σε προβολεα EPSON TW9200W.
Το αγορασα μονο και μονο για την ασφάλεια του προβολεα και επίτηδες πηρα 100w παραπανω ups απο τις αναγκες του Epson για να τον καλύπτει xωρις προβλημα .
Συμφωνα με τα τεχν.Χαρ. του ups ειναι για 480w και ο προβολεας σε φουλ λειτουργια ειναι 334w (δουλεύει ομως σε λειτουργια οικονομική στα 270w)
Τωρα με τις καταιγίδες που το χρειάστηκα 3 φορες σε διακοπες ρευματος ,και τις 3 φορες δεν μου κρατησε τον προβολεα ανοιχτο καθολου ,ετσι ωστε να μπωρεσω να τον κλείσω με ασφάλεια, ωστε να μην προκληθεί ζημια στον ιδιο και στην λαμπα λόγω θερμοκρασιας.
Για να το τσεκαρο καλυτερα ,εγινε δοκιμη του ups σε 60 πλασμα LG PB5600 με κατανάλωση ενέργειας σε λειτουργία: 154 Watt και δεν υπήρξε το παραμικρό προβλημα ,κράτησε κανονικά χρονο για να σβησει η τηλεόραση με ασφαλεια ,το ιδιο δε ,εγινε και σε δοκιμη σε μικροτερο προβολεα Εpson TW600 με κατανάλωση ενέργειας σε φουλ λειτουργία: 250 Watt ,κανονικά κράτησε ρευμα και εκει ,ετσι ωστε να απενεργοποιηθεί ο προβολεας με ασφαλεια
Λογικα ,με τα παραπανω παραδείγματα ,πανω απο 300w ,ΔΕΝ πρεπει να μπωρει να τα σηκωση και ας γραφη οτι ειναι μεχρι 480w.
Μετα απο e-mail που ελαβα απο την εταιρεια για το παραπανω ''προβλημα'':We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
In August, I bought the above ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W), to be installed EXCLUSIVELY on the EPSON TW9200W projector.
I bought it solely for the safety of the projector and intentionally chose a ups with 100w more than the Epson's requirements to cover it without any issues.
According to the ups technical specifications, it is for 480w and the projector operates at full capacity at 334w (though it operates in economy mode at 270w).
Now, with the storms that caused power outages, I needed it three times and all three times it did not keep the projector on at all, so I couldn't safely turn it off to avoid any damage to the projector and lamp due to temperature.
To check it better, a test was conducted on the ups with a 60-inch LG PB5600 plasma TV with power consumption in operation: 154 Watts and there was no problem at all, it held power normally until the TV safely turned off. The same test was done on a smaller Epson TW600 projector with power consumption in full operation: 250 Watts, and it held power normally there as well, so that the projector could be safely turned off.
Logically, with the above examples, it should not be able to handle more than 300w, even though it is stated to handle up to 480w.
After receiving an email from the company regarding the above "issue": We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
Τον Αυγουστο αγορασα το παραπανω ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W) ,για να τοποθετηθεί ΑΠΟΚΛΕΙΣΤΙΚΑ σε προβολεα EPSON TW9200W.
Το αγορασα μονο και μονο για την ασφάλεια του προβολεα και επίτηδες πηρα 100w παραπανω ups απο τις αναγκες του Epson για να τον καλύπτει xωρις προβλημα .
Συμφωνα με τα τεχν.Χαρ. του ups ειναι για 480w και ο προβολεας σε φουλ λειτουργια ειναι 334w (δουλεύει ομως σε λειτουργια οικονομική στα 270w)
Τωρα με τις καταιγίδες που το χρειάστηκα 3 φορες σε διακοπες ρευματος ,και τις 3 φορες δεν μου κρατησε τον προβολεα ανοιχτο καθολου ,ετσι ωστε να μπωρεσω να τον κλείσω με ασφάλεια, ωστε να μην προκληθεί ζημια στον ιδιο και στην λαμπα λόγω θερμοκρασιας.
Για να το τσεκαρο καλυτερα ,εγινε δοκιμη του ups σε 60 πλασμα LG PB5600 με κατανάλωση ενέργειας σε λειτουργία: 154 Watt και δεν υπήρξε το παραμικρό προβλημα ,κράτησε κανονικά χρονο για να σβησει η τηλεόραση με ασφαλεια ,το ιδιο δε ,εγινε και σε δοκιμη σε μικροτερο προβολεα Εpson TW600 με κατανάλωση ενέργειας σε φουλ λειτουργία: 250 Watt ,κανονικά κράτησε ρευμα και εκει ,ετσι ωστε να απενεργοποιηθεί ο προβολεας με ασφαλεια
Λογικα ,με τα παραπανω παραδείγματα ,πανω απο 300w ,ΔΕΝ πρεπει να μπωρει να τα σηκωση και ας γραφη οτι ειναι μεχρι 480w.
Μετα απο e-mail που ελαβα απο την εταιρεια για το παραπανω ''προβλημα'':We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.
In August, I bought the above ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W), to be installed EXCLUSIVELY on the EPSON TW9200W projector.
I bought it solely for the safety of the projector and intentionally chose a ups with 100w more than the Epson's requirements to cover it without any issues.
According to the ups technical specifications, it is for 480w and the projector operates at full capacity at 334w (though it operates in economy mode at 270w).
Now, with the storms that caused power outages, I needed it three times and all three times it did not keep the projector on at all, so I couldn't safely turn it off to avoid any damage to the projector and lamp due to temperature.
To check it better, a test was conducted on the ups with a 60-inch LG PB5600 plasma TV with power consumption in operation: 154 Watts and there was no problem at all, it held power normally until the TV safely turned off. The same test was done on a smaller Epson TW600 projector with power consumption in full operation: 250 Watts, and it held power normally there as well, so that the projector could be safely turned off.
Logically, with the above examples, it should not be able to handle more than 300w, even though it is stated to handle up to 480w.
After receiving an email from the company regarding the above "issue": We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
Τον Αυγουστο αγορασα το παραπανω ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W) ,για να τοποθετηθεί ΑΠΟΚΛΕΙΣΤΙΚΑ σε προβολεα EPSON TW9200W.
Το αγορασα μονο και μονο για την ασφάλεια του προβολεα και επίτηδες πηρα 100w παραπανω ups απο τις αναγκες του Epson για να τον καλύπτει xωρις προβλημα .
Συμφωνα με τα τεχν.Χαρ. του ups ειναι για 480w και ο προβολεας σε φουλ λειτουργια ειναι 334w (δουλεύει ομως σε λειτουργια οικονομική στα 270w)
Τωρα με τις καταιγίδες που το χρειάστηκα 3 φορες σε διακοπες ρευματος ,και τις 3 φορες δεν μου κρατησε τον προβολεα ανοιχτο καθολου ,ετσι ωστε να μπωρεσω να τον κλείσω με ασφάλεια, ωστε να μην προκληθεί ζημια στον ιδιο και στην λαμπα λόγω θερμοκρασιας.
Για να το τσεκαρο καλυτερα ,εγινε δοκιμη του ups σε 60 πλασμα LG PB5600 με κατανάλωση ενέργειας σε λειτουργία: 154 Watt και δεν υπήρξε το παραμικρό προβλημα ,κράτησε κανονικά χρονο για να σβησει η τηλεόραση με ασφαλεια ,το ιδιο δε ,εγινε και σε δοκιμη σε μικροτερο προβολεα Εpson TW600 με κατανάλωση ενέργειας σε φουλ λειτουργία: 250 Watt ,κανονικά κράτησε ρευμα και εκει ,ετσι ωστε να απενεργοποιηθεί ο προβολεας με ασφαλεια
Λογικα ,με τα παραπανω παραδείγματα ,πανω απο 300w ,ΔΕΝ πρεπει να μπωρει να τα σηκωση και ας γραφη οτι ειναι μεχρι 480w.
Μετα απο e-mail που ελαβα απο την εταιρεια για το παραπανω ''προβλημα'':We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
In August, I bought the above ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W), to be installed EXCLUSIVELY on the EPSON TW9200W projector.
I bought it solely for the safety of the projector and intentionally chose a ups with 100w more than the Epson's requirements to cover it without any issues.
According to the ups technical specifications, it is for 480w and the projector operates at full capacity at 334w (though it operates in economy mode at 270w).
Now, with the storms that caused power outages, I needed it three times and all three times it did not keep the projector on at all, so I couldn't safely turn it off to avoid any damage to the projector and lamp due to temperature.
To check it better, a test was conducted on the ups with a 60-inch LG PB5600 plasma TV with power consumption in operation: 154 Watts and there was no problem at all, it held power normally until the TV safely turned off. The same test was done on a smaller Epson TW600 projector with power consumption in full operation: 250 Watts, and it held power normally there as well, so that the projector could be safely turned off.
Logically, with the above examples, it should not be able to handle more than 300w, even though it is stated to handle up to 480w.
After receiving an email from the company regarding the above "issue": We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.
Τον Αυγουστο αγορασα το παραπανω ups (POWERWALKER VI 850 SH SCHUKO LED 850VA/480W) ,για να τοποθετηθεί ΑΠΟΚΛΕΙΣΤΙΚΑ σε προβολεα EPSON TW9200W.
Το αγορασα μονο και μονο για την ασφάλεια του προβολεα και επίτηδες πηρα 100w παραπανω ups απο τις αναγκες του Epson για να τον καλύπτει xωρις προβλημα .
Συμφωνα με τα τεχν.Χαρ. του ups ειναι για 480w και ο προβολεας σε φουλ λειτουργια ειναι 334w (δουλεύει ομως σε λειτουργια οικονομική στα 270w)
Τωρα με τις καταιγίδες που το χρειάστηκα 3 φορες σε διακοπες ρευματος ,και τις 3 φορες δεν μου κρατησε τον προβολεα ανοιχτο καθολου ,ετσι ωστε να μπωρεσω να τον κλείσω με ασφάλεια, ωστε να μην προκληθεί ζημια στον ιδιο και στην λαμπα λόγω θερμοκρασιας.
Για να το τσεκαρο καλυτερα ,εγινε δοκιμη του ups σε 60 πλασμα LG PB5600 με κατανάλωση ενέργειας σε λειτουργία: 154 Watt και δεν υπήρξε το παραμικρό προβλημα ,κράτησε κανονικά χρονο για να σβησει η τηλεόραση με ασφαλεια ,το ιδιο δε ,εγινε και σε δοκιμη σε μικροτερο προβολεα Εpson TW600 με κατανάλωση ενέργειας σε φουλ λειτουργία: 250 Watt ,κανονικά κράτησε ρευμα και εκει ,ετσι ωστε να απενεργοποιηθεί ο προβολεας με ασφαλεια
Λογικα ,με τα παραπανω παραδείγματα ,πανω απο 300w ,ΔΕΝ πρεπει να μπωρει να τα σηκωση και ας γραφη οτι ειναι μεχρι 480w.
Μετα απο e-mail που ελαβα απο την εταιρεια για το παραπανω ''προβλημα'':We suspect the beamer has APFC (power factor correction) and hence requires oversizing for this model. Generally all online models and line-interactive with pure sine wave output support APFC loads, but this does not apply to VI SH Series.