The Fluke CP-730 three-phase voltage monitor monitors the mains voltage and protects a single-phase load against overvoltage or undervoltage outside the set limits. The potentiometers adjust the lower and upper limits U1 and U2 for each of the three phases. When a limit is exceeded on any phase, the contact opens after the specified delay and closes automatically once the voltage returns to the acceptable range.
If at least 10 out-of-limit fluctuations occur within 1 minute, the relay locks out for 10 minutes. This status is indicated by a yellow LED.
- Type: Three-phase
- Rated contact current: 10 A
- Mounting: On a 35 mm DIN rail
- Contact: Isolated 1P
- Power supply: 3×(50÷450 V)+N
- Protection: Against overvoltage, undervoltage and phase sequence faults
- U1 trip limit: 150÷210 V
- U2 trip limit: 230÷260 V
- U1 return hysteresis: 5 V
- U2 return hysteresis: 5 V
- U1 trip delay: Adjustable from 0.5 to 10 s
- U2 trip delay: 0.1 s
- U1 return time: 1.0 s
- U2 return time: 1.0 s
- Power indicator: Green LED
- Voltage limit exceeded indicator: 2 red LEDs
- Lockout indicator: Yellow LED
- Power consumption: 1.7 W
- Operating temperature: -25 to 50 °C
- Connection: Screw terminals, 2.5 mm²
- Width: 3 modules (52.5 mm)
- Placement
- Rail
- Type
- Three-phase
- Rated Contact Current
- 10 A
- Digital
- No
- Protection Type
- Overvoltage, Undervoltage, Phase Sequence