The Kronos 11-01 level controller detects the presence of water via a circuit that closes when the motor ground is connected to the electrode through the pipe and water. It has a 2 min start-up delay to confirm that water is present after a power outage, and a 4 sec stop delay to prevent momentary interruptions.
When the pipe between the pump and the electrode is plastic, the electrode tee is grounded and positioned so that it will not continue to get wet in the event of a water outage.
- Sensitivity: 10 kΩ max
- Electrode voltage: 20 V AC max
- Electrode current: 2 mA max
- Supply voltage: 220 V AC ± 10%
- Maximum contact current: 10 A AC
- Type
- Level Control Relay
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.