The Hager CFA463J four-pole DIN-rail residual current device interrupts the circuit when it detects a leakage current of 300 mA. It operates at 230 V and is Type A.
- Rated current: 63 A
- Number of poles: 4
- Residual current: 300 mA
- Type: A
- Voltage: 230 V
- Number of modules: 4
- Rated impulse withstand voltage: 4 kV
- Rated insulation voltage: 500 V
- Rated frequency: 50 Hz
- Tightening torque: 2.8 Nm
- Connection: Screw
- Power loss at rated current: 19.7 W
- Electrical endurance: 2,000 cycles
- Mechanical endurance: 4,000 cycles
- Flexible cable cross-section: 16 mm²
- Solid cable cross-section: 25 mm²
- Operating temperature: From -25 to 40 °C
- Storage temperature: From -55 to 70 °C
- Height: 83 mm
- Width: 70 mm
- Depth: 70 mm
- Type
- Earth Leakage
- Number of Poles
- 4
- Voltage
- 230 V
- Nominal Voltage
- 63 A
- Leakage Current
- 300 mA
- with Energy Consumption Meter
- No
- with Timer
- No
- Type of Residual Current Relay
- Type A
Important information