The Schneider Electric A9F04301 miniature circuit breaker is three-pole and designed for distribution circuits in AC and DC networks. It uses thermal-magnetic tripping technology with a C tripping curve and is mounted on a DIN rail.
- Number of poles: 3
- Rated current: 1 A
- Networks: AC and DC
- Tripping curve: C
- Tripping technology: Thermal-magnetic
- Application: Distribution circuits
- Icu breaking capacity: 10 kA at 125...180 V DC, 50 kA at 12...133 V AC, 25 kA at 440 V AC, 50 kA at 380...415 V AC and 220...240 V AC
- Icn breaking capacity: 6000 A at 400 V AC 50/60 Hz
- Utilization category: A according to IEC 60898-1 and EN 60898-1
- Isolation function: According to IEC 60947-2, IEC 60898-1, EN 60947-2 and EN 60898-1
- Frequency: 50/60 Hz
- Magnetic tripping threshold: 8 x In +/- 20%
- Ics: 100% x Icu
- Limitation class: 3
- Ui: 500 V AC 50/60 Hz
- Uimp: 6 kV
- Contact position indication: Yes
- Operation: Lever, with local trip indication
- Mounting: DIN rail
- Dimensions: 91 × 54 × 78.5 mm
- Weight: 0.375 kg
- Color: White
- Mechanical endurance: 20,000 cycles
- Electrical endurance: 10,000 cycles
- Terminals: Double, top or bottom
- Flexible cable connection: 1...16 mm²
- Rigid cable connection: 1...25 mm²
- Wire stripping length: 14 mm
- Tightening torque: 2 N·m
- Earth leakage protection: With a separate block
- Standards: EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2
- Degree of protection: IP20 according to EN 60529 and IEC 60529
- Pollution degree: 3
- Overvoltage category: IV
- Tropicalization: 2
- Relative humidity: 95% at 55 °C
- Operating temperature: -35...70 °C
- Storage temperature: -40...85 °C
Specifications
- Number of Poles
- 3
- Rated Current
- 1 A
- Operating Curve
- Curve C
Power Supply
- AC
- Yes
- DC
- Yes
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.