The TSD-1 point smoke and heat detector is designed to detect the early stage of a developing fire. Equipped with a photoelectric visible smoke detector and an excessive differential temperature sensor, it ensures high sensitivity and non-directionality.
The precise Hexamesh stainless steel filter protects against dirt and small insects. Its connection to alarm control panels with a 12 V power supply is made easy thanks to the configuration using micro-switches and built-in parametric resistors.
Device Features:- Unique Swirl chamber for faster smoke detection
- Smoke detection according to EN54-7 requirements
- Heat detection according to EN54-5
- Mode selection switches (smoke, heat, multi-sensors)
- Line type selection: NO/NC/2EOL using switches
- Hexamesh precision filter made of stainless steel
- Chamber pollution indication
- Easy mounting on the base
- Compatibility with any 12 V alarm control panel
- Power supply voltage (±15%): 12 V DC
- Enclosure dimensions: ø108 x 61 mm
- Operating temperature range: -10…+55 °C
- Standby current consumption: 250 µA
- Maximum current consumption: 24 mA
- Weight: 164 g
- Permissible load on relay contacts (resistive): 40 mA / 16 V DC
- Maximum humidity: 93 ±3%
- Classification according to EN 54-5 (thermal sensor): A1R
- Minimum static alarm temperature: 54 °C
- Maximum static alarm temperature: 65 °C
- Environmental class according to EN50130-5: II
Dimensions
- Type
- Smoke Detector
- Thread
- No
- Autonomous
- No
- Zones Number
- 12
Smart Features
- Smart Ecosystem
- -
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.