The Schneider Electric iC60H circuit breaker is intended for distribution applications in AC and DC networks. It uses thermal-magnetic technology, has a C tripping curve and provides isolation.
- Type: Circuit breaker
- Range: Acti 9
- Poles: 1P
- Protected poles: 1
- Rated current (In): 10 A
- Tripping curve: C
- Magnetic tripping: 8 x In +/- 20 %
- Breaking capacity (Icu): 20 kA at 12...60 V DC, 15 kA at 72 V DC, 30 kA at 100...133 V AC 50/60 Hz, 42 kA at 12...60 V AC 50/60 Hz and 15 kA at 220...240 V AC 50/60 Hz, according to IEC/EN 60947-2
- Breaking capacity (Icn): 10000 A at 230 V AC 50/60 Hz, according to IEC/EN 60898-1
- Category: A
- Frequency: 50/60 Hz
- Rated insulation voltage (Ui): 500 V AC 50/60 Hz
- Rated impulse withstand voltage (Uimp): 6 kV, according to IEC 60947-2 and EN 60947-2
- Indications: Contact position and tripping
- Mounting: DIN rail
- Width: 2 modules of 9 mm
- Dimensions: 91 × 18 × 78.5 mm
- Weight: 0.125 kg
- Colour: White
- Mechanical endurance: 20000 cycles
- Electrical endurance: 10000 cycles
- Flexible conductor cross-section: 1...16 mm²
- Rigid conductor cross-section: 1...25 mm²
- Stripping length: 14 mm
- Tightening torque: 2 N.m
- Standards: EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2
- Degree of protection: IP20
- Pollution degree: 3
- Overvoltage category: IV
- Tropicalisation: 2
- Operating humidity: 95 % at 55 °C
- Operating temperature: -35...70 °C
- Storage temperature: -40...85 °C