The Eastron SDM630 M Modbus energy meter is a three-phase meter equipped with an RS-485 port and a certified MID Modbus-RTU protocol. It includes two pulse outputs, one of which is adjustable. The meter measures and displays supply characteristics of single-phase with two wires (1p2w), three-phase with three wires (3p3w), and three-phase with four wires (3p4w).
The measured parameters include:
- Voltage (V)
- Frequency (Hz)
- Current (A)
- Capacity (kW/kVA/kVAR)
- Consumed energy (import)
- Supplied energy (export)
- Total energy (kWh/kVARh)
Additionally, it indicates peak current flow and power demand, measured at adjustable intervals from 1 to 60 minutes. The meter operates with a load up to 100A and does not require connection to current transformers (CT).
Technical specifications:
- AC Voltage (Un): 3x230(400)V
- Voltage range: 80 ~ 120% Un
- Base current (Ib): 10A
- Maximum current (Imax): 100A
- Minimum current (Imin): 0.3A
- Starting current: 0.4% Ib
- Power consumption: 2W/10VA (voltage measurement circuit), 4VA (current measurement circuit)
- Voltage accuracy: 0.5% of full scale
- Current accuracy: 0.5% of nominal current
- Frequency accuracy: 0.2% of average frequency
- Power factor accuracy: 1% of the unit (0.01)
- Active power accuracy (W): 1% of full scale
- Reactive power accuracy (VAR): 1% of full scale
- Apparent power accuracy (VA): 1% of full scale
- Active energy (Wh): Class 1 IEC 62053-21
- Reactive energy (VARh): 1% of full scale
- Signal response time: 1 second input step, typically above 99% of final reading at 50 Hz
- Operating temperature: -40°C to 70°C
- Storage temperature: -40°C to 70°C
- Relative humidity: 0 to 95% non-condensing
- Altitude: up to 2000 m above sea level
- Warm-up time: 5 seconds
- Vibration: 10Hz to 50Hz, 2g, IEC 60068-2-6
- Shock: 30g
- Protection class: IP51 (indoor)
- Material: Self-extinguishing UL94 V-0
- Display: 400 Imp/kWh
- Dimensions (DIN): 72 x 100 mm (width x height) according to DIN 43880
- Mounting rail: DIN (DIN 43880)
Specifications
- Display Type
- Analog
- Installation Type
- Rail
- Number of Phases
- Three-phase
Smart Features
- Connectivity
- Modbus
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.