The Eastron SDM630-M three-phase energy analyzer measures and displays electrical power parameters, including voltage, frequency, current, active, reactive and apparent power, as well as imported and exported energy. It supports single-phase two-wire, three-phase three-wire and three-phase four-wire systems. The RS-485 port allows readings to be retrieved via Modbus-RTU.
It also records peak current and power demand over programmable intervals from 1 to 60 minutes. It operates with loads of up to 100 A without current transformers and has two pulse outputs, one of which is configurable.
- Type: Energy analyzer
- Display type: Digital
- Installation type: DIN rail
- Number of phases: Three-phase
- Connectivity: Modbus-RTU via RS-485
- Maximum current: 100 A
- AC voltage: 3 × 230 (400) V
- Voltage range: 80–120% of rated voltage
- Basic current: 10 A
- Minimum current: 0.3 A
- Starting current: 0.4% of basic current
- Measured parameters: Voltage, frequency, current, active, reactive and apparent power, imported and exported energy
- Peak and power demand measurement interval: 1–60 minutes, programmable
- Pulse outputs: 2, one configurable
- Voltage accuracy: 0.5% of full scale
- Current accuracy: 0.5% of rated current
- Frequency accuracy: 0.2% of mid-frequency
- Power factor accuracy: 1% of unity (0.01)
- Active power accuracy: 1% of full scale
- Reactive power accuracy: 1% of full scale
- Apparent power accuracy: 1% of full scale
- Active energy class: Class 1 IEC 62053-21
- Reactive energy accuracy: 1% of full scale
- Response time: 1 second for an input step change, typically reaching more than 99% of the final reading at 50 Hz
- Operating temperature: −40 to 70 °C
- Storage temperature: −40 to 70 °C
- Relative humidity: 0–95%, non-condensing
- Maximum operating altitude: 2,000 m above sea level
- Warm-up time: 5 seconds
- Vibration: 10–50 Hz, 2 g, IEC 60068-2-6
- Shock resistance: 30 g
- Protection rating: IP51, for indoor use
- Material: Self-extinguishing, UL94 V-0
- Pulse indication: 400 pulses/kWh
- Dimensions: 72 × 100 mm (width × height), according to DIN 43880
Specifications
- Type
- Energy Analyzer
- Display Type
- Digital
- Installation Type
- Rail
- Number of Phases
- Three-phase
- Maximum Current
- 100 A
Smart Features
- Connectivity
- Modbus
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.