Description
Specifications
Technical Features
- Architecture: 1P+N
- Curve: C
- Protection: Residual current type AC
- Protection category (IP): IP2X
-
Main electrical characteristics:
- Rated short-circuit breaking capacity Icn AC according to IEC 60898-1: 6 kA
-
Connectivity:
- Connection type: Terminal codes
-
Voltage:
- Rated insulation voltage Ui: 500 V
- Rated impulse withstand voltage Uimp: 4,000 V
- Maximum operating voltage: 240 V
- Rated operational voltage Ue: 240 - 240 V
- Overvoltage category according to IEC 60947-1: 3
- Power supply voltage type: AC
-
Electrical current:
- Rated current: 20 A
- Rated residual operating current Idn: 30 mA
- Rated current -25°C: 22.70 A
- Rated current -20°C: 22.50 A
- Rated current -15°C: 22.20 A
- Rated current -10°C: 22 A
- Rated current -5°C: 21.80 A
- Rated current 0°C: 21.50 A
- Rated current 5°C: 21.30 A
- Rated current 10°C: 21 A
- Rated current 15°C: 20.80 A
- Rated current 20°C: 20.50 A
- Rated current 25°C: 20.30 A
- Rated current 30°C: 20 A
- Rated current 35°C: 19.80 A
- Rated current 40°C: 19.60 A
- Rated current 45°C: 19.40 A
- Rated current 50°C: 19.20 A
- Rated current 55°C: 19 A
- Rated current 60°C: 18.80 A
- Correction factor for current for 2 devices side by side: 1
- Minimum/maximum threshold value of AC thermal operation: 1.13 - 1.45 A
- Correction factor for current for 3 devices side by side: 0.95
- Correction factor for current for 4 and 5 devices side by side: 0.90
- Correction factor for current for 6 devices side by side: 0.85
- Rated service breaking capacity Ics AC according to IEC 60898-1: 6 kA
- Type
- Earth Leakage
- Voltage
- 500 V
- Nominal Voltage
- 20 A
- Leakage Current
- 30 mA
- Type of Residual Current Relay
- -
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.