Name: Digital Voltage Protection Relay, Single-Phase
Model: SVP-917-63A
- Important Functions: overvoltage protection, undervoltage protection, overcurrent protection, energy consumption display (kWh), adjustable range 1–63 A, automatic reset.
Technical Specifications:
- Current protection range: 1 – 63 A (default 40 A; option up to 80 A with special order)
- Adjustable overvoltage limit: 85 – 300 V (default ~270 V)
- Adjustable undervoltage limit: 85 – 300 V (default ~170 V)
- Startup delay time: 2 – 255 s (default 2 s)
- Power consumption (voltage circuit): ~1 W, weight < 1 VA
- Active energy display: 0 – 9999.9 kWh
- Current/voltage accuracy: ±0.5 %
- Active energy accuracy: ±1 % (according to IEC62053-21 standard)
- Rated frequency: 50 / 60 Hz
- Operating temperature: –25 °C … +70 °C
- Storage temperature: –40 °C … +80 °C
- Permissible relative humidity: ≤ 85 %
- Maximum operating altitude: up to 2,500 m
- Dimensions (L × W × H): approximately 100 × 36 × 67.5 mm
- Material: combined plastic and metal housing
Features and Operation:
- Overvoltage protection: The relay disconnects the power supply if the voltage exceeds the set limit.
- Undervoltage protection: The relay disconnects if the voltage falls below the set limit.
- Overcurrent protection: The circuit is automatically protected if the current exceeds the set limit between 1–63 A.
- Consumption display (kWh): Total consumption is shown on the digital display.
- Automatic reset: After disconnection, power is restored automatically when conditions return to normal.
- Dual current/voltage display: Continuous monitoring of operating parameters.
- Warning codes: Display of the latest fault codes for easy diagnosis.
Installation and Operating Instructions:
- Mounting: on a 35 mm DIN rail inside an electrical panel.
- Connections:
- Input: phase (L) and neutral (N) from the mains.
- Output: phase and neutral to the protected circuit.
- Initial settings:
- Overvoltage and undervoltage limits.
- Current limit.
- Startup delay time.
- After power-up: check the displays (voltage, current, consumption).
- Disconnection tests can be performed with controlled voltage variation or temporary overload.
Safety Recommendations and Terms:
- Check the wiring before sealing.
- Ensure that the load does not exceed the specified protection current.
- Use only a properly connected and verified receiver, without improper contact.
- If protection is activated, disconnect the load to avoid repeated connection/disconnection cycles.
- This device does not replace a short-circuit breaker; use together with one is recommended.
- Display Type
- Digital
- Installation Type
- Rail
- Number of Phases
- Single-phase