The product concerns the Overvoltage Protector T2 4P 40kA 1.35kV TT-TNS with auxiliary contact SPE440R from Hager. Below are the technical specifications:
- Nominal operating voltage (Ue): 240 / 415 V
- Frequency: 50/60 Hz
- Maximum continuous operating voltage (Uc): 275 V
- Lightning protection level (Up) according to IEC61643-1: 1.35 kV
- Protection level Up L-PE / N-PE according to standard IEC 61643-11: 1.5 kV
- Protection device size preceding: 125 A
- Network type: TT/TN-S
- Installed product depth: 58.2 mm
- Installed product height: 89.8 mm
- Installed product width: 71.2 mm
- Clamping torque: 3Nm
- Cross-section of single-core conductor for upper and lower terminal connections: 1.5 / 35 mm²
- Flexible conductor cross-section for upper and lower terminal connections: 1.5 / 25 mm²
- Approvals: KEMA, NF
- IEC61643-11 / VDE0675-6-11 class: T2
- European WEEE directive: applicable
- Operating temperature: -40…80 °C
- Product Number
- SPE440R
- Number of Poles
- 4
- Type
- T2
- Replacement Cartridge
- No
- Maximum Discharge Current (kA)
- 40
Important information