The F&F CKF-BT-TRMS DIN rail relay monitors phase loss, phase asymmetry and phase sequence to protect three-phase electric motors. It disconnects the motor when it detects a fault and features an adjustable disconnection delay.
It automatically reactivates when the voltage rises 5 V above the activation threshold. It mounts on a 35 mm DIN rail and connects via screw terminals.
- Rated current: 10 A
- Operating voltage: 400 V
- Power supply: 3 × 400 V + N
- Voltage asymmetry activation threshold: 40–80 V
- Voltage hysteresis: 5 V
- Disconnection delay: 0.5–5 s
- Protection rating: IP20
- Dimensions: 2 modules (35 mm)
- Operating temperature: −25–40 °C
- Connection: 4 mm² screw terminals
- Power consumption: 1.6 W
- Certification: CE
- with Energy Consumption Meter
- No
- with Timer
- No
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.